This is the OEM-specified draft inducer pressure switch for the Carrier PY4GEAB36060AA packaged unit. The pressure switch is a critical safety component that monitors negative pressure created by the inducer motor to confirm proper venting before allowing the ignition sequence to proceed. When this switch fails or sticks open, the control board cannot verify safe flue-gas exhaust, triggering a system lockout — the most common symptom is the furnace or packaged unit attempting to start, then shutting down immediately with no heat delivered. A failed inducer, cracked hose, or blocked drain can also mimic a bad switch, so always verify inducer operation and hose integrity before condemning this part.
Compatibility: Designed for the Carrier PY4GEAB36060AA packaged unit. Also fits select Carrier, Bryant, and Payne models requiring a 0.18" W.C. normally-open draft pressure switch — verify your unit's data plate and existing switch rating before ordering. Note: OEM part number HK06WC061 has been superseded by HK06MB061; this listing covers both the original and successor specification. Questions about fitment? Our HVAC parts team confirms compatibility before you buy.