Same-day shipping before 3PM CST · 35,000+ OEM Parts · Texas CMBL & SAM.gov Registered · Government POs Accepted

Menu

Home Shop All Account Cart
OEM Carrier Pressure Switch 0.18
Carrier

OEM Carrier Pressure Switch 0.18" WC SPST for PY3GPAA42090NA

SKU: CARRIE-PY3GPAA42090NA-PRESSURE_SWITCH-HK06WC061 Brand: Carrier
Guaranteed to fit PY3GPAA42090NA — or your money back. Terms

OEM Guaranteed

Same-Day Ship

30-Day Returns

Secure Checkout

Texas CMBL #19328542014
SAM.gov Registered
Govt POs Accepted

OEM Carrier Draft Pressure Switch 0.18" WC SPST for Model PY3GPAA42090NA

This OEM draft inducer pressure switch (part number HK06WC061, current updated replacement: HK06MB061) is the factory-specified replacement for the Carrier PY3GPAA42090NA packaged gas unit. The pressure switch proves that the inducer motor has established proper negative pressure (draft) before allowing the control board to energize the igniter and open the gas valve. When this switch fails or becomes stuck open, the furnace or packaged unit will lock out before ignition — often displaying a fault code for a failed pressure switch — leaving you with no heat and a frustrating no-start condition.

  • Specs: 0.18" Water Column (W.C.) setpoint | SPST (Single-Pole Single-Throw) | Normally Open | Replaces Honeywell IS20224-5236 | OEM part HK06WC061 superseded by HK06MB061
  • OEM vs Generic: OEM pressure switches are calibrated to the exact W.C. rating required by your unit's heat exchanger design. An off-spec generic switch can open too early or too late, causing nuisance lockouts or — more dangerously — allowing combustion without confirmed draft.
  • Install difficulty: 2/5 — Power down the unit and confirm zero voltage before starting. Tools needed: #2 Phillips screwdriver, 1/4" nut driver, needle-nose pliers. Disconnect the rubber tubing and two spade terminals, swap the switch, reconnect, and verify operation through a full call-for-heat cycle.
  • Warranty: 1-year OEM factory warranty against defects. Ships same business day from our stocked warehouse.

Compatibility: Engineered as a direct OEM fit for Carrier PY3GPAA42090NA packaged gas/electric units. Also fits select Bryant and Payne models using the same 0.18" W.C. SPST draft switch. Always confirm the W.C. rating on your existing switch or unit data plate before ordering. Have questions about fit? Our HVAC parts specialists verify compatibility before you buy — order with confidence and get it shipped today.

Shipping Information

  • Orders placed before 3PM CST ship same business day
  • Standard delivery: 2-5 business days
  • Express shipping available at checkout
  • Free shipping on orders over $99
  • Tracking number emailed upon shipment

Return Policy

  • 30-day returns on unused parts in original packaging
  • Electrical parts (capacitors, contactors, control boards) are final sale once installed
  • Email info@nationalhvacparts.com to initiate a return
  • Refunds processed within 5-7 business days

Frequently Asked Questions

Does this Pressure Switch fit my Carrier PY3GPAA42090NA?
Yes. This is the factory-specified OEM pressure switch for the Carrier PY3GPAA42090NA. It is a direct drop-in replacement that fits without modification. Always verify the model number on your equipment nameplate before ordering.
How do I replace the pressure switch on my Carrier PY3GPAA42090NA?
Difficulty: Medium (20–30 min)
Step 1: Turn off power. Step 2: Locate pressure switch near draft inducer. Step 3: Note tubing orientation. Step 4: Disconnect tubing and wires. Step 5: Remove screw, install new switch. Step 6: Reconnect tubing and wires, restore power.
My furnace shows a pressure switch error. What do I replace?
Furnace LED showing pressure switch error = switch not detecting draft inducer airflow. Try first: clear the rubber tubing to the switch (often clogged with condensation). If problem persists, replace the pressure switch.
Is this pressure switch compatible with Bryant or Payne too?
Many Carrier parts are cross-compatible with Bryant and Payne since all three brands are manufactured by Carrier Global Corporation. The same physical part is often used across brand labels with different model numbers. To verify: check your Bryant or Payne equipment service manual for cross-compatible part numbers, or email info@nationalhvacparts.com with your model number.
Should I use OEM or aftermarket for my Carrier pressure switch?
OEM recommended for reliability and warranty compatibility. OEM parts match exact factory specifications for proper fit, performance, and safety. While aftermarket alternatives cost less upfront, the risk of improper fit and reduced lifespan usually makes OEM the better value long-term.
How fast does National HVAC Parts ship?
Orders placed before 3:00 PM CST ship the same business day. Standard delivery is 2–5 business days anywhere in the continental United States. Express shipping available at checkout. We ship from Houston, TX to all 50 states. 30-day return policy on all parts.