Order before 3PM CST — ships same day.
Standard delivery 2-5 business days. Express options at checkout.
OEM Guaranteed
Same-Day Ship
30-Day Returns
Secure Checkout
This OEM Carrier draft pressure switch is the factory-specified replacement for the Carrier PY3GNA060115NA gas furnace. The pressure switch monitors negative pressure created by the inducer motor during the pre-purge cycle. If adequate draft is not proven, the switch prevents the ignition sequence from proceeding — protecting the system from unsafe operation. A failed pressure switch typically causes the furnace to lockout before ignition, often with a diagnostic fault code indicating a pressure switch error. You may also observe the inducer motor running continuously while the burners never light.
Compatibility: Designed for the Carrier PY3GNA060115NA gas furnace. Also fits select Bryant and Payne models sharing the HK06WC061 / HK06MB061 specification — verify your unit's data plate W.C. rating before ordering. Not sure if this part fits? Our HVAC parts specialists verify fitment before you order — contact us today.