This is the genuine OEM Carrier flame sensor (part #50HJ401431), factory-specified for the Carrier PY1RPA120224ABWA packaged gas heating unit. The flame sensor is a critical safety component: after ignition, the control board sends a small microamp current through the sensor's stainless steel rod into the burner flame. If the board does not detect that return current within a few seconds, it cuts gas flow and locks out the system. A failed or carbon-coated flame sensor is one of the most common causes of a furnace that lights briefly, then shuts off after 5–8 seconds — often followed by a lockout fault code.
Compatibility: Engineered as a direct OEM drop-in replacement for the Carrier PY1RPA120224ABWA packaged gas/electric unit. Always confirm your existing part number against the unit data plate or wiring diagram before ordering. Our parts specialists are available to verify fitment — contact us before you buy if you have any questions.