Pressure switch did not close — blocked vent, bad inducer, or stuck switch.
Brand: Carrier (Also covers Bryant, Payne) | Equipment: Gas Furnace
Code 31 means the pressure switch did not close after the inducer motor started. When the inducer runs, it creates negative pressure that should close the switch. If it doesn't close in 5 minutes, the inducer shuts down for 15 minutes before retrying.
What: Snow, ice, birds nests, or a disconnected pipe block proper venting.
How to check: Visually inspect the exhaust outlet outside the house.
Fix: Clear the blockage.
Shop partsWhat: Inducer doesn't spin or spins too slowly to create the needed pressure.
How to check: Listen for inducer hum or grinding; should run smoothly.
Fix: Replace inducer motor.
Shop partsWhat: Switch contacts don't close even when proper pressure exists.
How to check: Tech can test with manometer.
Fix: Replace pressure switch.
Shop partsWhat: Water buildup or kinks in the tubing prevent the switch from sensing pressure.
How to check: Inspect rubber/plastic tubing run.
Fix: Clear water, replace tubing.
Try our interactive symptom diagnostic tool or browse Carrier parts.