The Goodman 20162903 is a genuine OEM primary limit switch with a 150°F set point for AMS80805CXAB gas furnaces. Mounted on the heat-exchanger/blower bulkhead, this auto-reset control opens the gas/ignition circuit if supply-air temperature climbs past its rating — the furnace's front-line protection against overheating from restricted airflow. When temperatures fall back into range, it recloses automatically. A failed primary limit is a common cause of short-cycling or a furnace that won't fire.
The trip temperature and mounting geometry are calibrated to this furnace. Generic limits at a different set point can nuisance-trip on normal operation or allow the exchanger to overheat. For a primary safety control, OEM is strongly recommended.
Difficulty: Easy. Shut off power and gas, unplug the spade terminals, remove the two mounting screws, and install the replacement in the same position and orientation. Usually 10–20 minutes. If the switch had been tripping, correct the airflow restriction (clogged filter, closed dampers, weak blower) before returning to service.
Confirm your model number before ordering. Backed by our fast-ship guarantee.