{"product_id":"oem-goodman-high-pressure-cut-off-switch-for-wph4360ahbb-0130m00074","title":"OEM Goodman High Pressure Cut-Off Switch for WPH4360AHBB — 0130M00074","description":"\u003cp\u003eThe \u003cstrong\u003eGoodman 0130M00074 High Pressure Cut-Off Switch\u003c\/strong\u003e is a genuine OEM safety control for \u003cstrong\u003eWPH4360AHBB\u003c\/strong\u003e packaged heat pumps. Wired into the compressor control circuit and mounted on the high (discharge) side, it opens to shut the compressor down when head pressure spikes—protecting against a dirty condenser coil, failed fan, or overcharge. It's an auto-reset control that re-closes once pressure drops back to a safe level.\u003c\/p\u003e\u003ch3\u003eSpecifications\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eType: High pressure cut-off switch (SPST, opens on rise)\u003c\/li\u003e\n\u003cli\u003eTrip (open): approx. 610 PSIG\u003c\/li\u003e\n\u003cli\u003eReset (close): approx. 420 PSIG (auto-reset)\u003c\/li\u003e\n\u003cli\u003eFunction: Compressor high-side overpressure protection\u003c\/li\u003e\n\u003cli\u003eFit: Goodman\/Amana WPH4360AHBB packaged heat pump\u003c\/li\u003e\n\u003cli\u003eOEM Part Number: 0130M00074\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch3\u003eOEM vs. Generic\u003c\/h3\u003e\u003cp\u003eThe \u003cstrong\u003eOEM 0130M00074\u003c\/strong\u003e is calibrated to the exact trip\/reset set points this system was designed for. A generic switch with different set points can nuisance-trip in cooling or, worse, fail to open in time and let the compressor run into a dangerous overpressure. When the part is a safety device guarding the compressor, use the OEM calibration.\u003c\/p\u003e\u003ch3\u003eInstallation Difficulty: Easy to Moderate\u003c\/h3\u003e\u003cp\u003eThe switch typically threads onto a Schrader-style port or clamps to the line and connects via two spade terminals. On a Schrader fitting, \u003cstrong\u003ethe valve reseals as you remove the switch, so little to no refrigerant is lost\u003c\/strong\u003e. Cut power first and confirm the terminal wiring. On brazed-in versions, refrigerant recovery is required—verify your connection type before ordering service.\u003c\/p\u003e","brand":"Goodman","offers":[{"title":"Default Title","offer_id":63058258690419,"sku":"GOODMAN-15004","price":34.95,"currency_code":"USD","in_stock":true}],"url":"https:\/\/nationalhvacparts.com\/products\/oem-goodman-high-pressure-cut-off-switch-for-wph4360ahbb-0130m00074","provider":"National HVAC Parts","version":"1.0","type":"link"}