{"product_id":"icp-transformer-for-wpg3424090lkc1-208-230v-to-24v-40va-ships-today-1","title":"ICP Transformer for WPG3424090LKC1 — 208\/230V to 24V 40VA | Ships Today","description":"\u003ch3\u003eOverview\u003c\/h3\u003e\n\u003cp\u003eThis OEM control transformer steps the 208\/230V line voltage on your ICP WPG3424090LKC1 system down to the 24V control voltage that runs the thermostat, ignition control, contactor coil, and gas valve. Rated at 40VA, it supplies the low-voltage power the entire control circuit depends on. When a transformer fails, the unit goes completely dead on the control side — no call for heat or cool will energize anything, the thermostat may go blank, and you will often find a blown low-voltage fuse or burnt secondary winding. A buzzing, overheating, or open-winding transformer is a common no-heat \/ no-cool culprit. Includes the 24V barrier (part 1178431) used with this transformer assembly.\u003c\/p\u003e\n\n\u003ch3\u003eSpecifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eSpec\u003c\/th\u003e\n\u003cth\u003eValue\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e1173691 (TRANS), 1178431 (24V Barrier)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eType\u003c\/td\u003e\n\u003ctd\u003eControl Transformer\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eICP \/ Heil \/ Tempstar\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePrimary Voltage\u003c\/td\u003e\n\u003ctd\u003e208 \/ 230V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSecondary Voltage\u003c\/td\u003e\n\u003ctd\u003e24V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRating\u003c\/td\u003e\n\u003ctd\u003e40 VA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFit\u003c\/td\u003e\n\u003ctd\u003eOEM Replacement\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eCompatibility\u003c\/h3\u003e\n\u003cp\u003eDirect-fit OEM replacement for the ICP \/ Heil \/ Tempstar \/ Comfortmaker WPG3424090LKC1 packaged unit. Also fits many ICP-family models that use the 208\/230V-to-24V 40VA control transformer. Verify your existing transformer's VA and voltage ratings before ordering.\u003c\/p\u003e\n\n\u003ch3\u003eInstallation Guide\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eSafety First\u003c\/strong\u003e — Disconnect power at the disconnect and breaker, then verify zero voltage with a multimeter at the transformer terminals.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAccess\u003c\/strong\u003e — Remove the control\/blower access panel to reach the control box.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDocument\u003c\/strong\u003e — Photograph all primary and secondary wire connections before disconnecting.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRemove\u003c\/strong\u003e — Label and disconnect the primary (line) and secondary (24V) leads, then unbolt the transformer from the control panel.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInstall\u003c\/strong\u003e — Mount the new transformer, reconnect the primary taps for your supply voltage (208 or 230V) and the 24V secondary leads per your photo.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTest\u003c\/strong\u003e — Restore power and confirm 24V across the secondary terminals and normal system operation.\u003c\/li\u003e\n\u003c\/ol\u003e\n\n\u003ch3\u003eSigns You Need a Replacement\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eNo 24V control voltage — system completely dead on the low-voltage side\u003c\/li\u003e\n\u003cli\u003eRepeatedly blown low-voltage fuse or tripped breaker\u003c\/li\u003e\n\u003cli\u003eAudible buzzing, overheating, or a burnt smell from the transformer\u003c\/li\u003e\n\u003cli\u003eOpen or shorted winding when checked with a multimeter\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eShipping \u0026amp; Returns\u003c\/h3\u003e\n\u003cp\u003eShips same day before 3 PM CST. 30-day returns. Backed by the National HVAC Parts fitment guarantee.\u003c\/p\u003e","brand":"ICP","offers":[{"title":"OEM","offer_id":63027219497331,"sku":"1178431","price":41.6,"currency_code":"USD","in_stock":true},{"title":"Generic","offer_id":63047750779251,"sku":"1178431-GEN","price":32.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0984\/1190\/5395\/files\/nhvac-transformer-control-1178431_0b83cddf-19d1-454f-bfed-d045f9937949.jpg?v=1782896762","url":"https:\/\/nationalhvacparts.com\/products\/icp-transformer-for-wpg3424090lkc1-208-230v-to-24v-40va-ships-today-1","provider":"National HVAC Parts","version":"1.0","type":"link"}