{"product_id":"icp-ecm-x-13-fan-motor-for-wpa3244000rkc1-1-2-hp-ships-today-1","title":"ICP ECM X-13 Fan Motor for WPA3244000RKC1 — 1\/2 HP | Ships Today","description":"\u003ch3\u003eOverview\u003c\/h3\u003e\n\u003cp\u003eThis OEM ECM X-13 motor control (part number 1185842) is the 1\/2 HP variable-speed blower motor used in the ICP WPA3244000RKC1 air handler\/blower section. X-13 motors are constant-torque ECM (electronically commutated) motors that deliver quieter operation, lower energy use, and better airflow consistency than legacy PSC motors. The integrated control module reads the tap selected by the furnace or air handler board and holds a programmed torque to maintain airflow across changing static pressure. Common failure symptoms include a blower that won't start, intermittent operation, a motor that runs hot and cycles on thermal overload, error codes from the control board, or unusual humming and no rotation. Because the module and motor are matched as an assembly, replacing with the correct OEM X-13 unit ensures proper torque tables and tap response.\u003c\/p\u003e\n\n\u003ch3\u003eSpecifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eSpec\u003c\/th\u003e\n\u003cth\u003eValue\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e1185842\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eType\u003c\/td\u003e\n\u003ctd\u003eECM X-13 Constant-Torque Motor Control\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eICP \/ Heil \/ Tempstar \/ Comfortmaker\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHorsepower\u003c\/td\u003e\n\u003ctd\u003e1\/2 HP\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMotor Technology\u003c\/td\u003e\n\u003ctd\u003eElectronically Commutated (ECM)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eApplication\u003c\/td\u003e\n\u003ctd\u003eFurnace \/ Air Handler Blower\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFits Model\u003c\/td\u003e\n\u003ctd\u003eWPA3244000RKC1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eCompatibility\u003c\/h3\u003e\n\u003cp\u003eDirect OEM replacement for the 1\/2 HP ECM X-13 blower motor in the ICP\/Heil\/Tempstar\/Comfortmaker WPA3244000RKC1. Verify horsepower, motor diameter, shaft size, rotation, and the multi-pin control connector against your existing assembly before installing, as X-13 motors are programmed for specific equipment torque profiles.\u003c\/p\u003e\n\n\u003ch3\u003eInstallation Guide\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eSafety First\u003c\/strong\u003e — Disconnect power at the breaker and disconnect, then verify zero voltage with a multimeter before touching the motor.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAccess\u003c\/strong\u003e — Remove the blower compartment service panel and slide out the blower assembly.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDocument\u003c\/strong\u003e — Photograph the line voltage plug, the control plug, and the selected speed taps before disconnecting.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRemove\u003c\/strong\u003e — Mark the blower wheel set-screw position, loosen it, pull the old motor from the housing, and transfer the wheel and mounting band.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInstall\u003c\/strong\u003e — Mount the new X-13 motor, reinstall the blower wheel at the same depth, and reconnect the line and control plugs per your photos.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTest\u003c\/strong\u003e — Restore power and run the blower on each call (heat, cool, fan) to confirm proper ramp-up and airflow.\u003c\/li\u003e\n\u003c\/ol\u003e\n\n\u003ch3\u003eSigns You Need a Replacement\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eBlower won't start or runs intermittently\u003c\/li\u003e\n\u003cli\u003eMotor overheats and trips on thermal overload\u003c\/li\u003e\n\u003cli\u003eHumming with no rotation or wrong direction\u003c\/li\u003e\n\u003cli\u003eWeak airflow or control-board fault codes\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eShipping \u0026amp; Returns\u003c\/h3\u003e\n\u003cp\u003eShips same day before 3 PM CST. 30-day returns. Backed by the National HVAC Parts fitment guarantee.\u003c\/p\u003e","brand":"ICP","offers":[{"title":"OEM","offer_id":63027228574067,"sku":"1185842","price":245.7,"currency_code":"USD","in_stock":true},{"title":"Generic","offer_id":63047519928691,"sku":"1185842-GEN","price":189.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0984\/1190\/5395\/files\/nhvac-blower-motor-ecm-1185842_9bb04fc3-5a3d-4577-a09c-fb00cab7d1f0.jpg?v=1782887865","url":"https:\/\/nationalhvacparts.com\/products\/icp-ecm-x-13-fan-motor-for-wpa3244000rkc1-1-2-hp-ships-today-1","provider":"National HVAC Parts","version":"1.0","type":"link"}