{"product_id":"icp-3-pole-35a-contactor-for-rh5420424-24v-coil-ships-today","title":"ICP 3-Pole 35A Contactor for RH5420424 — 24V Coil | Ships Today","description":"\u003ch3\u003eOverview\u003c\/h3\u003e\n\u003cp\u003eThis genuine OEM 3-pole definite-purpose contactor (Part #1280465) fits ICP, Heil, and Tempstar condensing units, including model RH5420424. The contactor is the electrically operated switch that energizes the compressor and condenser fan motor on a call for cooling. When its 24-volt coil is energized, the three sets of 35-amp contacts close to deliver line voltage to the outdoor unit. Three-pole contactors are common on three-phase or higher-capacity equipment where all power legs are switched simultaneously. Burned, pitted, or welded contacts and a failed coil are leading causes of no-cooling and compressor-won't-start service calls.\u003c\/p\u003e\n\u003ch3\u003eSpecifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eSpec\u003c\/th\u003e\n\u003cth\u003eValue\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e1280465\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eType\u003c\/td\u003e\n\u003ctd\u003eDefinite-Purpose Contactor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eICP \/ Heil \/ Tempstar\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePoles\u003c\/td\u003e\n\u003ctd\u003e3-Pole\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eContact Rating\u003c\/td\u003e\n\u003ctd\u003e35 Amps\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoil Voltage\u003c\/td\u003e\n\u003ctd\u003e24V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003eCompatibility\u003c\/h3\u003e\n\u003cp\u003eDirectly fits ICP\/Heil\/Tempstar model RH5420424 and related ICP-family condensing units and heat pumps using a 3-pole, 35A, 24V-coil contactor. Confirm the existing part number, pole count, and footprint before ordering.\u003c\/p\u003e\n\u003ch3\u003eInstallation Guide\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eSafety First\u003c\/strong\u003e — Disconnect power at the disconnect and breaker, then verify zero voltage with a multimeter.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAccess\u003c\/strong\u003e — Remove the condensing unit service panel.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDocument\u003c\/strong\u003e — Photograph all wire connections before disconnecting anything.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRemove\u003c\/strong\u003e — Transfer line, load, and 24V coil leads one at a time and unbolt the old contactor from its bracket.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInstall\u003c\/strong\u003e — Mount the new contactor and reconnect all line, load, and coil wires per your photo.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTest\u003c\/strong\u003e — Restore power, call for cooling, and verify the contactor pulls in and the unit starts.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003ch3\u003eSigns You Need a Replacement\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eOutdoor unit won't start or only hums\u003c\/li\u003e\n\u003cli\u003eBurned, pitted, or welded contacts\u003c\/li\u003e\n\u003cli\u003eLoud chattering or buzzing\u003c\/li\u003e\n\u003cli\u003eUnit won't shut off due to stuck-closed contacts\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eShipping \u0026amp; Returns\u003c\/h3\u003e\n\u003cp\u003eShips same day before 3 PM CST. 30-day returns. Backed by the National HVAC Parts fitment guarantee.\u003c\/p\u003e","brand":"ICP","offers":[{"title":"Direct Replacement","offer_id":63027267142003,"sku":"1280465-GEN","price":34.95,"currency_code":"USD","in_stock":true},{"title":"OEM","offer_id":63047948370291,"sku":"1280465","price":45.44,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0984\/1190\/5395\/files\/nhvac-contactor-3pole-1280465_fc629359-898c-4e7f-b32a-cc40e0a2c4d0.jpg?v=1782882167","url":"https:\/\/nationalhvacparts.com\/products\/icp-3-pole-35a-contactor-for-rh5420424-24v-coil-ships-today","provider":"National HVAC Parts","version":"1.0","type":"link"}