{"product_id":"icp-2-pole-30a-contactor-for-rhs090h0cb0aaa-24v-coil-ships-today","title":"ICP 2-Pole 30A Contactor for RHS090H0CB0AAA — 24V Coil | Ships Today","description":"\u003ch3\u003eOverview\u003c\/h3\u003e\n\u003cp\u003eThis OEM 2-pole, 30-amp contactor is the main switching relay for the ICP\/Tempstar\/Heil RHS090H0CB0AAA heat pump. Its 24V coil is energized by the thermostat through the control transformer; when it pulls in, the contacts close and route line voltage to the compressor and condenser fan motor. Over thousands of cycles the silver contacts pit, burn, and weld, while the coil can open or overheat. A failing contactor causes hard starts, chattering, buzzing, intermittent cooling, or a unit that will not start at all. Replacing a worn contactor restores clean, reliable switching and protects the compressor from low-voltage and single-phasing damage.\u003c\/p\u003e\n\n\u003ch3\u003eSpecifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\u003ctr\u003e\n\u003cth\u003eSpec\u003c\/th\u003e\n\u003cth\u003eValue\u003c\/th\u003e\n\u003c\/tr\u003e\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003ePrimary OEM Part\u003c\/td\u003e\n\u003ctd\u003e1178074\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eType\u003c\/td\u003e\n\u003ctd\u003eDefinite Purpose Contactor, 2-Pole\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eICP \/ Tempstar \/ Heil\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eContact Rating\u003c\/td\u003e\n\u003ctd\u003e30A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePoles\u003c\/td\u003e\n\u003ctd\u003e2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoil Voltage\u003c\/td\u003e\n\u003ctd\u003e24V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFit\u003c\/td\u003e\n\u003ctd\u003eOEM Direct Replacement\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eCompatibility\u003c\/h3\u003e\n\u003cp\u003eDirect-fit replacement for the ICP\/Tempstar\/Heil RHS090H0CB0AAA heat pump. For higher-load builds in this series a 40A 2-pole equivalent (OEM 1178211) is also used — confirm the amp rating and coil voltage stamped on your existing contactor before ordering.\u003c\/p\u003e\n\n\u003ch3\u003eInstallation Guide\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eSafety First\u003c\/strong\u003e — Disconnect power at the breaker and unit disconnect, then verify zero voltage with a multimeter.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAccess\u003c\/strong\u003e — Remove the service panel to reach the contactor in the control compartment.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDocument\u003c\/strong\u003e — Photograph every line, load, and coil wire before disconnecting.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRemove\u003c\/strong\u003e — Transfer wires one at a time, or label them, then unscrew the old contactor from the bracket.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInstall\u003c\/strong\u003e — Mount the new contactor and reconnect each wire exactly per your photo.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTest\u003c\/strong\u003e — Restore power and confirm the contactor pulls in cleanly on a cooling call with no chatter.\u003c\/li\u003e\n\u003c\/ol\u003e\n\n\u003ch3\u003eSigns You Need a Replacement\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eLoud buzzing, humming, or chattering from the contactor\u003c\/li\u003e\n\u003cli\u003ePitted, burnt, or welded contacts visible on inspection\u003c\/li\u003e\n\u003cli\u003eCompressor and fan fail to start or start intermittently\u003c\/li\u003e\n\u003cli\u003e24V at the coil but contacts do not pull in\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eShipping \u0026amp; Returns\u003c\/h3\u003e\n\u003cp\u003eShips same day before 3 PM CST. 30-day returns. Backed by the National HVAC Parts fitment guarantee.\u003c\/p\u003e","brand":"ICP","offers":[{"title":"Direct Replacement","offer_id":63021888962931,"sku":"1178074-GEN","price":29.0,"currency_code":"USD","in_stock":true},{"title":"OEM","offer_id":63047929528691,"sku":"1178074","price":37.7,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0984\/1190\/5395\/files\/nhvac-contactor-2pole-1178074_a3204277-8d7b-42c3-adb1-808231bd85ea.jpg?v=1782881091","url":"https:\/\/nationalhvacparts.com\/products\/icp-2-pole-30a-contactor-for-rhs090h0cb0aaa-24v-coil-ships-today","provider":"National HVAC Parts","version":"1.0","type":"link"}